With the implementation of China’s “dual carbon” strategy, the installed capacity of new energy has grown rapidly. Wind power and photovoltaic power have accounted for more than 40%, but the integration of power electronic apparatus into the grid has resulted in the manifestation of a system with “low inertia and weak damping”, which can easily lead to transient overvoltage problems at transmitters when high-voltage direct-current (HVDC) latching faults occur. Although a variety of dynamic reactive power optimization strategies have been proposed in the existing research, most of them are aimed at single equipment, and multi-reactive power source collaborative control schemes are lacking. In this paper, we innovatively establish a transient voltage analysis model for a new energy transmitter, derive the expression of overvoltage amplitude, and propose a method for the construction of a multi-reactive source collaborative optimization model, which can effectively suppress transient overvoltage through capacity and initial output configuration. We provide a new idea for the safe operation of a significant percentage of new energy grids. The case analysis shows that the co-optimization method outlined in this paper is an effective solution to suppress the transient overvoltage triggered by AC faults and has wide application value.